AMC 2026 catalogue

HVAC & Refrigeration

Heating Cables

Find even MORE at Grainger.ca 1951

1-888-602-0000 HVAC & REFRIGERATION

Electric Pipe Heating Cable Approved for all types of metal pipe and CSA-approved plastic pipes including ABS, CPVC and Polybutylene. Cable has a tough PVC inner insulation and continuous ground braid for safety. Weather resistant PVC (high-low temperature) outer jacket. 3-wire grounded cord and plug, 23 watts/ meter (7 watts/foot) at design conditions. Moisture proof automatic thermostat energizes when freezing conditions are detected. cUL listed, CSA approved.

SNLAHB016

Voltage Watts per Cable @ 40F Cable Length

Item

No. 120V AC 42 W 6 ft SNLAHB016 120V AC 63 W 9 ft SNLAHB019 120V AC 84 W 12 ft SNLAHB112 120V AC 105 W 15 ft SNLAHB115 120V AC 126 W 18 ft SNLAHB118 120V AC 168 W 24 ft SNLAHB124 120V AC 210 W 30 ft SNLAHB130 120V AC 280 W 40 ft SNLAHB140 120V AC 420 W 60 ft SNLAHB160 120V AC 500 W 80 ft SNLAHB180

EASYHEAT

EasyHeat Commercial Self- Regulating Pre-Terminated Cable

Commercial PSR cable is a parallel, self regulating cable provided in pre-terminated lengths with factory sealed connections. Made with a water resistant TPE outer jacket. Rated at 5 watts per foot at 10° C. 120 volt with a three wire plug with pilot light. CSA certified.

SNLPSR1006

Cable Length Watts per Cable @ 40F

Item

No. 6 ft 30 W SNLPSR1006 12 ft 60 W SNLPSR1012 18 ft 90 W SNLPSR1018 50 ft 250 W SNLPSR1050 75 ft 375 W SNLPSR1075 100 ft 500 W SNLPSR1100

EASYHEAT

Self-Regulating Pipe Heating and Roof/Gutter De-Icing Cable

▪Cut-to-length in the field ▪No thermostat needed 100-ft. complete kits include cable, 2 power connection kits (No. WWG4E519), 1 splice and tee kit, and 1 roll of application tape (No. WWG4E521). CSA Certified for U.S. and Canada only when used with the appropriate agency-approved Raychem components and accessories. Watts/ft/ @ 40 F on insulated pipe.

Note: Use only Raychem accessories; install per instructions supplied with No. WWG4E519. Also, all pipe heating applications require the use of pipe insulation material.

WARNING: To minimize the danger of fire if the heating cable is damaged or improperly installed, use a Ground- Fault-Protection Device (GFPD).

WWG2VEV6

WWG4E512

Item Includes Item No.

Permanent Power Connection Kit All Materials Needed for One Hard Wired Power Connection into Standard Junction Box, End Seal WWG4E519

Application Tape (1) Roll Glass Cloth Tape 66 ft L, 1⁄2 in W, (10) Electric Trace Labels WWG4E521 Gel Filled End Seal Kit (2) End Seals WWG4YZ41

‡ Max. 200 ft. in ice and snow. # Max. 400 ft. in ice and snow.

Mounting Location Heater Voltage Includes

Watts per Foot @ 40F

Amps per Foot @ 40F Max. Circuit Length

Item

No. Electric Heating Cable

Dry 120 VAC Cable Only 6 W 0.05 A 200 ft WWG2VEV6 240 VAC Cable Only 6 W 0.03 A 350 ft WWG2VEV7 Electric Heating Cable Kit

Dry 120 VAC Power Connection Kit, Roll of Application Tape, Splice and Tee Kit 6 W 0.05 A 200 ft WWG4E512 240 VAC Power Connection Kit, Roll of Application Tape, Splice and Tee Kit 6 W 0.03 A 350 ft WWG4E514 Electric Heating Cable

Wet or Dry

120 VAC Cable Only 6 W 0.05 A 200 ft WWG2VEV8‡ 120 VAC Cable Only 6 W 0.05 A 200 ft WWG4E515‡ 240 VAC Cable Only 6 W 0.03 A 400 ft WWG4E517# Electric Heating Cable Kit

Wet or Dry 120 VAC Power Connection Kit, Roll of Application Tape, Splice and Tee Kit 6 W 0.05 A 200 ft WWG4E516‡

RAYCHEM

Dry Location, 6W—Designed for more demanding residential/commercial applications on plastic or metal pipes up to 6" dia.

Wet or Dry Location, 6W—Has a protective, waterproof outer jacket suitable for wet conditions such as downspouts, roof drains, or marine applications. Use on metal and plastic pipes up to 6" dia. Also good for roof and gutter applications when used with clip accessory Nos. WWG5JC37, WWG5JC39, and WWG5JC41.

Application Tape—Attaches heating cable to pipe. Use a minimum of 1 label every 10 ft.